Honeywell placa de retea HC900 Manual

Manuale PDF
228 Pagini Română

Honeywell placa de retea HC900
Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output
Revision 5 HC900 Hybrid Controller Installation and User Guide 195
9/03
4 Point Analog Output
Step Action
4 Connect field wiring.
1 2 3 4 5 6 7 8 9
10
11
12
13
14
15 16 17
18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
LOAD
LOAD
LOAD
LOAD
AO-1
AO-2
AO-4
AO-3
LOADS ARE 0 to 750 ohm
A
O1
+
A
O1
-
A
O4
+
A
O4
-
A
O2
+
A
O2
-
A
O3
+
A
O3
-
16 Point Contact Digital Input
Step Action
1 ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 60).
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.
Connect desired cable to 16 point Contact DI module at controller. Choose from:
900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
Install DI module label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 60).
2 Mount RTP to DIN rail.
Latch to rail. See page 205.
Connect cable to RTP